ADAM 4000 Series
3-14
ADAM
ADAM-4021
Analog Output Module
Analog Output
Effective resolution: 12-bit
Output type: mA, V
Output range: 0 to 20 mA, 4 to 20 mA,
and 0 to 10 V
Isolation voltage: 3000 V
DC
Output Impedance: 0.5
Accuracy:
±0.1% of FSR for current output
±0.2% of FSR for voltage output
Readback accuracy: ±1% of FSR
Resolution: ±0.015% of FSR
Zero drift:
Voltage output: ±30 µV/°C
Current output: ±0.2 µA/°C
Span temperature coefficient:
±25 ppm/°C
Programmable output slope:
0.125 ~ 128 mA/sec.
0.0625 ~ 64.0 V/sec.
Current load resistor:
0 to 500 (source)
Built-in Watchdog Timer
Power
Power requirements:
+10 ~ +30 V
DC
(non-regulated)
Power consumption: 1.4 W
ADAM-4018M
8-Channel Analog Input
Data Logger
Analog Input
Effective resolution: 16-bit
Channels:
Six differential, two single-ended
lnput type: Thermocouple, mV, V, mA
lnput range: ±15 mV, ±50 mV, ±100
mV, ±500 mV, ±1 V, ±2.5 V, ±20 mA
T/C type and temperature range:
J 0 ~ 760° C
K 0 ~ 1370° C
T -100 ~ 400° C
E 0 ~ 1000° C
R 500 ~ 1750° C
S 500 ~ 1750° C
B 500 ~ 1800° C
Isolation voltage: 3000 V
DC
Sampling rate: 10 samples/sec. (total)
Input impedance: 1.8 M
Bandwidth: 13.1 Hz @ 50 Hz,
15.72 Hz @ 60 Hz
Accuracy: ±0.1% or better
Zero drift: ±3 µV/°C
Span drift: ±25 ppm/°C
CMR @ 50/60 Hz: 92 dB min.
Storage
Capacity (128KB Flash memory):
38,000 samples (total)
Storage mode: Write to end of
memory & cyclic
Logging mode: Internal log or event
log (high/low)
Sampling interval: 2 secs. ~ 18 hours
Built-in Watchdog Timer
Power
Power requirements:
+10 ~ +30 V
DC
(non-isolated)
Power consumption: 1.8 W
ADAM-4018
8-Channel Thermocouple
Input Module
Analog Input
Effective resolution: 16-bit
Channels:
Six differential, two single-ended
lnput type: Thermocouple, mV, V, mA
lnput range: ±15 mV, ±50 mV, ±100
mV, ±500 mV, ±1 V, ±2.5 V, ±20 mA
T/C type and temperature range:
J 0 ~ 760° C
K 0 ~ 1370° C
T -100 ~ 400° C
E 0 ~ 1000° C
R 500 ~ 1750° C
S 500 ~ 1750° C
B 500 ~ 1800° C
Isolation voltage: 3000 V
DC
Fault and overvoltage protection:
Withstands overvoltage up to ±35 V
Sampling rate: 10 samples/sec. (total)
Input impedance: 20 M
Bandwidth: 13.1 Hz @ 50 Hz,
15.72 Hz @ 60 Hz
Accuracy: ±0.1% or better
Zero drift: ±3 µV/°
C
Span drift: ±25 ppm/°C
CMR @ 50/60 Hz: 92 dB min.
Built-in Watchdog Timer
Power
Power requirements:
+10 ~ +30 V
DC
(non-isolated)
Power consumption: 0.8 W
ADAM-4018 8-Channel Thermocouple Input Module