Advantech RS-100-RT Manuel d'utilisateur

Naviguer en ligne ou télécharger Manuel d'utilisateur pour Serveurs Advantech RS-100-RT. Advantech RS-100-RT User`s manual [en] [es] [fr] Manuel d'utilisatio

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 398
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs

Résumé du contenu

Page 1 - ADAM 4000

ADAM 4000SeriesData Acquisition ModulesUser's Manual

Page 2

1-4 ADAM 4000 Series User's ManualIntroductionThe RS-485 network, together with screw-terminal plug connectors, allowsfor system expansion, recon

Page 3 - ADAM 4000 Series

Command Set4-16 ADAM 4000 Series User's ManualADAM-4017+ Command SetCommand SyntexCommandResponseSyntexCommand DescriptionCommandExampleCommandre

Page 4 - Table of Contents

Chapter 4 Command Set 4-17Chapter 4Command SyntexCommandResponseSyntexCommand DescriptionCommandExampleCommandresponseExample$AA1Ci(cr)i: 0 ~ 7

Page 5

Command Set4-18 ADAM 4000 Series User's ManualRangecode(Hex)Input Range Max. Signal Min SignalDisplayedResolution07 +/-4~20 mA +20.000 -20.000 1u

Page 6

Chapter 4 Command Set 4-19Chapter 4ADAM-4018 Command TableCommand Syntax Command Name Command Description Page No.%AANNTTCCFF Configuration Set

Page 7 - Introduction

Command Set4-20 ADAM 4000 Series User's ManualADAM-4018+ Command SetCommand SyntexCommandResponseSyntexCommand DescriptionCommandExampleCommandre

Page 8 - 1.1 Overview

Chapter 4 Command Set 4-21Chapter 4Command SyntexCommandResponseSyntexCommand DescriptionCommandExampleCommandresponseExample#AA(cr) >(data0

Page 9

Command Set4-22 ADAM 4000 Series User's ManualCommand SyntexCommandResponseSyntexCommand DescriptionCommandExampleCommandresponseExample$AAM(cr)

Page 10

Chapter 4 Command Set 4-23Chapter 4Command Syntax Command Name Command Description Page No.%AANNTTCCFF Configuration Set the address, input ran

Page 11 - Installation Guideline

Command Set4-24 ADAM 4000 Series User's ManualADAM-4019 Command TableCommand Syntax Command Name Command Description Page No.%AANNTTCCFF Configur

Page 12

Chapter 4 Command Set 4-25Chapter 4Command Syntax Command Name Command Description Page No.%AANNTTCCFF Configuration Set the address, output ra

Page 13

2Installation Guideline

Page 14 - Power Supply Connections

Command Set4-26 ADAM 4000 Series User's ManualCommand Syntax Command Name Command Description Page No.%AANNTTCCFF Configuration Sets address, bau

Page 15

Chapter 4 Command Set 4-27Chapter 4ADAM-4051 Command Set TableNote: For command sets and further application, please link toAdvantech’s web sit

Page 16 - +10~+30 V

Command Set4-28 ADAM 4000 Series User's ManualCommand Syntax Command Name Command Description Page No.%AANNTTCCFF Configuration Sets address, bau

Page 17

Chapter 4 Command Set 4-29Chapter 4Command Syntax Command Name Command Description Page No.%AANNTTCCFF Configuration Sets address, baud rate, a

Page 18

Command Set4-30 ADAM 4000 Series User's ManualADAM-4055 Command Set TableCommand Syntax Command Name Command Description Page No.%AANNTTCCFF Conf

Page 19 - 2.3 Baud rate and Checksum

Chapter 4 Command Set 4-31Chapter 4Command Syntax Command Name Command Description Page No.%AANNTTCCFF Configuration Sets address, baud rate, a

Page 20 - Grounding the INIT* Terminal

Command Set4-32 ADAM 4000 Series User's ManualCommand Syntax Command Name Command Description Page No.%AANNTTCCFF Configuration Sets the address,

Page 21 - 2.4 Multiple Module Hookup

Chapter 4 Command Set 4-33Chapter 4Command Syntax Command Name Command Description Page No.$AAAG Set Gate Mode Requests the specified counter/f

Page 22 - 2.5 Application Example

Command Set4-34 ADAM 4000 Series User's ManualCommand Syntax Command Name Command Description Page No.$AA4S Enable/DisableDigital FilterEnables o

Page 23 - Figure 2-5

Chapter 4 Command Set 4-35Chapter 4Command Syntax Command Name Command Description Page No.@AAPN(data) Set Initial CountValue of Counter NSets

Page 24

2-2 ADAM 4000 Series User's ManualInstallation GuidelineThis chapter provides guidelines to what is needed to set up and install anADAM ne

Page 25

Command Set4-36 ADAM 4000 Series User's ManualCommand Syntax Command Name Command Description Page No.%AANNTTCCFF Configuration Sets the address,

Page 26

Chapter 4 Command Set 4-37Chapter 4Command Syntax Command Name Command Description Page No.$AAAG Set Gate Mode Requests the specified counter/f

Page 27 - I/O Modules

Command Set4-38 ADAM 4000 Series User's ManualCommand Syntax Command Name Command Description Page No.$AA4S Enable/Disable DigitalFilterEnables o

Page 28

Chapter 4 Command Set 4-39Chapter 4Command Syntax Command Name Command Description Page No.@AAEAT Enable Alarm Enable the alarm in eithermoment

Page 29

Command Set4-40 ADAM 4000 Series User's Manual

Page 30

Chapter 4 Command Set 4-41Chapter 4Command Syntax Command Name Description I/O Module%AANNTTCCFF Configuration Sets the address, inputrange, b

Page 31

4-42 ADAM 4000 Series User's ManualCommand SetCommandSyntaxCommand Name Description I/O Module$AA6 Read ChannelStatusAsk the specified inputmodul

Page 32

Chapter 4 Command Set 4-43Chapter 4CommandSyntaxCommand Name Command Description I/O Module$AA0CiSingle ChannelSpan CalibrationCalibrates a sp

Page 33 - ADAM-4012 Analog Input Module

4-44 ADAM 4000 Series User's ManualFigure 4-1 Data format for 8-bit parameter%AANNTTCCFFName ConfigurationDescription Sets address, input range

Page 34 - ADAM-4013 RTD Input Module

Chapter 4 Command Set 4-45%AANNTTCCFFResponse !AA(cr) if the command is valid.?AA(cr) if an invalid parameter was entered or if the INIT*termi

Page 35 - Thermocouple Input

Chapter 2 Installation Guideline 2-3Chapter 22.1 System Requirements to set up an ADAM networkThe following list gives an overview of what is

Page 36 - Process Current Input

4-46 ADAM 4000 Series User's ManualTable 4-1 Input Range Codes (Type Code)Input Range Code (Hex) Input Range for 4011,4011D,4018,4018+,4018M00 ±

Page 37 - RTD Inputs

Chapter 4 Command Set 4-47Input Range Code (Hex) Input Range for 401320 Platinum, -100o to 100oC, α=0.0038521 Platinum, 0o to 100oC, α=0.00385

Page 38

4-48 ADAM 4000 Series User's Manual$AA2Name Configuration StatusDescription The command requests the return of the configuration datafrom the ana

Page 39 - Application Wiring

Chapter 4 Command Set 4-49$AA2Example command: $452(cr)response: !45050600(cr)The command asks the analog input module at address 45h tosend i

Page 40

4-50 ADAM 4000 Series User's Manual$AAFName Read Firmware VersionDescription The command requests the analog input module at address AAto return

Page 41

Chapter 4 Command Set 4-51$AAMName Read Module NameDescription The command requests the analog input module at address AAto return its nameSyn

Page 42

4-52 ADAM 4000 Series User's Manual#AAName Analog Data InDescription The command will return the input value from a specified (AA)module in the c

Page 43

Chapter 4 Command Set 4-53Twos complement % of Span Engineering unitsunder-limit 0000 -0000 -0000over-limit FFFF +9999 +9999#AAExample command

Page 44 - Strain Gauge Current Input

4-54 ADAM 4000 Series User's Manual4015, 4017, 4017+, 4018,4018+, 4018M, 4019#AANName Read Analog Input from Channel NDescription The command wil

Page 45 - Digital Output used with SSR

Chapter 4 Command Set 4-55$AA5VVName Enable/disable channels for multiplexingDescription Enables/disables multiplexing simultaneously for sepe

Page 46 - Input Modules

2-4 ADAM 4000 Series User's ManualInstallation GuidelineAssume that a +24 VDC will be used to power five ADAM-4011 AnalogInput Modules. T

Page 47

4-56 ADAM 4000 Series User's Manual$AA6Name Read Channel StatusDescription Asks a specified input module to return the status of allchannelsSynta

Page 48 - ADAM-4017

Chapter 4 Command Set 4-57$AA0Name Span CalibrationDescription Calibrates an analog input module to correct for gain errors.Syntax $AA0(cr)$ i

Page 49 - Figure 3-17

4-58 ADAM 4000 Series User's Manual$AA1Name Offset Calibration.Description Calibrates an analog input module to correct for offset errors.Syntax

Page 50 - JP9, Jp10

Chapter 4 Command Set 4-59#**Name Synchronized SamplingDescription Orders all analog input modules to sample their input valuesand store the v

Page 51 - ADAM-4018

4-60 ADAM 4000 Series User's Manual$AA4Name Read Synchronized DataDescription Returns the input value that was stored in the addressedmodule’s re

Page 52 - ADAM-4018M

Chapter 4 Command Set 4-61Example command: $074(cr)response: >071+5.8222(cr)The command asks the analog input module at address 07h tosend

Page 53 - Figure 3-20

4-62 ADAM 4000 Series User's Manual$AABName Channel DiagnoseDescription Diagnose channel status in over range, under range, and wireopeningSyntax

Page 54

Chapter 4 Command Set 4-63$AA3Name CJC Status commandDescription Instructs the addressed analog input module to read its CJC(Cold Junction Com

Page 55 - Apllication Wiring

4-64 ADAM 4000 Series User's Manual$AA9Name CJC Offset CalibrationDescription Calibrates an analog input module to adjust for offset errors ofits

Page 56

Chapter 4 Command Set 4-65$AA0CiName Single Channel Span CalibrationDescription The command calibrates a specified channel to correct for gain

Page 57 - T/C or 4~20mA

Chapter 2 Installation Guideline 2-5Chapter 2Communication WiringWe recommend that shielded-twisted-pair cables that comply with the EIARS-485

Page 58 - INPUT RANGE

4-66 ADAM 4000 Series User's Manual$AA1CiName Single Channel Offset CalibrationDescription The command calibrates a specified channel to correct

Page 59 - –0~20 mA

Chapter 4 Command Set 4-67$AA7CiRrrName Single Channel Range ConfigurationDescription This command configure the input type and range of thesp

Page 60

4-68 ADAM 4000 Series User's ManualCommand SetADAM-4015 command codes against Input ranges tableIEC RTD 100O, α = 0.00385JIS RTD 100O, α = 0.0039

Page 61

Chapter 4 Command Set 4-69Chapter 4ADAM-4019 command codes against Input ranges tableTable 4-3 Input Range Code for ADAM-4015 and ADAM-4019Com

Page 62

4-70 ADAM 4000 Series User's Manual$AA8CiName Read Single Channel Range ConfigurationDescription This command read the input type and range confi

Page 63 - Analog Output

Chapter 4 Command Set 4-71$AAXnnnnName Watchdog Timer SettingDescription This command set the Watchdog Timer communication cycle.Syntax $AAXnn

Page 64

4-72 ADAM 4000 Series User's Manual$AAYName Read Watchdog Timer SettingDescription This command read the setting of Watchdog Timer communica-tion

Page 65 - ADAM-4050 Digital I/O Module

Chapter 4 Command Set 4-734015$AAS0Name Internal CalibrationDescription This command execute Internal self-calibration for offset andgain erro

Page 66

4-74 ADAM 4000 Series User's Manual$AAS1Name Reload Default Calibrating ParameterDescription Reload factory default calibrating parameter to ove

Page 67

Chapter 4 Command Set 4-75$AAAiName CJC SettingDescription This command configure the CJC setting.Syntax $AAAi(cr)$ is a delimiter character.A

Page 68 - INIT*DI15

2-6 ADAM 4000 Series User's ManualInstallation GuidelineFigure 2-2 Basic Hook-up of ADAM Module to Host SwitchesThe following items are

Page 69

4-76 ADAM 4000 Series User's ManualCommand Set

Page 70

Chapter 4 Command Set 4-77Chapter 44014DCommand Syntax Command Name DescriptionI/OModule$AA3 Read SourceHigh/Low Valuesfor Linear MappingRead

Page 71 - TTL Input (ADAM-4050)

4-78 ADAM 4000 Series User's ManualCommand Set4014D$AA3Name Read Source High/Low Values for Linear MappingDescription Read the high/low limit val

Page 72 - Figure 3-38

Chapter 4 Command Set 4-79Chapter 44014D$AA3Example command: $133(cr)response: !13+04.000+20.000(cr)The module is configured for an ±20 mA in

Page 73 - Figure 3-40

4-80 ADAM 4000 Series User's ManualCommand Set4014D$AA5Name Read Target High/Low Values for Linear MappingDescription Read the mapped input high/

Page 74 - Wet Contact Input (ADAM-4053)

Chapter 4 Command Set 4-81Chapter 44014D$AA5Example command: $135(cr)response: !13+000.000+200.00(cr)The module is configured for a ±20mA inpu

Page 75

4-82 ADAM 4000 Series User's ManualCommand Set4014D$AA6(data_A)(data_B)Name Write Source High/Low Values for Linear MappingDescription Write the

Page 76 - ADAM-4060 Relay Output Module

Chapter 4 Command Set 4-83Chapter 44014D$AA6(data_A)(data_B)Example command: $136+04.000+20.000(cr)response: !13(cr)The module is configured f

Page 77 - TYPE SIGNAL

4-84 ADAM 4000 Series User's ManualCommand Set4014D$AA7(data_C)(data_D)Name Write Target High/Low Values for Linear MappingDescription Write the

Page 78

Chapter 4 Command Set 4-85Chapter 44014D$AA7(data_C)(data_D)Example command: $137+000.00+200.00(cr)response: !13(cr)The module is configured f

Page 79

Chapter 2 Installation Guideline 2-7Chapter 2Configuration with the ADAM Utility SoftwareThe easiest way to configure the ADAM module is by us

Page 80

4-86 ADAM 4000 Series User's ManualCommand Set4014D$AAAVName Enable/Disable Linear MappingDescription Enables or disables the linear mapping func

Page 81

Chapter 4 Command Set 4-87Chapter 44014D$AA8VName Select LED Data OriginDescription Select whether LED will display data from the input modul

Page 82 - ADAM-4080

4-88 ADAM 4000 Series User's ManualCommand Set4014D$AA9(data)Name Send LED DataDescription PC sends data to LED display. This command is valid on

Page 83 - ADAM-4080D

Chapter 4 Command Set 4-894018MChapter 4Command SyntaxCommandNameDescription I/O Module@AACCCSDMTTTT Set MemoryConfigurationSet the channel

Page 84 - Photo-isolated Input

4-90 ADAM 4000 Series User's ManualCommand Set4018MBit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0@AACCCSDMTTTTName Set Memory ConfigurationDescr

Page 85

Chapter 4 Command Set 4-914018MChapter 4@AACCCSDMTTTTResponse !AA(cr) if the configuration is successful.?AA(cr) if the configuration fails

Page 86 - 4.2 Syntax

4-92 ADAM 4000 Series User's ManualCommand Set4018M@AADName Read Memory ConfigurationDescription The command requests the configuration data from

Page 87

Chapter 4 Command Set 4-934018MChapter 4@AASOName Set Memory Operation ModeDescription Sets the operation mode of the analog input data log

Page 88 - ADAM-4011 Command Table

4-94 ADAM 4000 Series User's ManualCommand Set4018M@AATName Read Memory Operation ModeDescription Request the memory operation status of the anal

Page 89

Chapter 4 Command Set 4-954018MChapter 4@AALName Event Record CountDescription Request the number of event records stored in the analog inp

Page 90 - ADAM-4011D Command Table

2-8 ADAM 4000 Series User's ManualInstallation GuidelineTo change the configuration setting of the analog input module, thefollowing comma

Page 91

4-96 ADAM 4000 Series User's ManualCommand Set4018M@AANName Standard Record CountDescription Request the number of standard records stored in the

Page 92 - ADAM-4012 Command Table

Chapter 4 Command Set 4-974018MChapter 4Bit 3 Bit 2 Bit 1 Bit 0@AARNNNNName Read Record ContentDescription Request the content of record NN

Page 93

4-98 ADAM 4000 Series User's ManualCommand Set4018M@AARNNNNHHHH represents the 4-character hexadecimal number ofreturned record stored in the ana

Page 94 - ADAM-4013 Command Table

Chapter 4 Command Set 4-994018MChapter 4@AAACSDHHHHTEIIIIName Set Alarm LimitDescription Set high/low alarm limits for the channel C in the

Page 95 - ADAM-4015 Command Table

4-100 ADAM 4000 Series User's ManualCommand Set4018M@AAACSDHHHHTEIIIIExample command: @EFA0020400020100(cr)response: !EF(cr)The command sets chan

Page 96 - ADAM-4016 Command Table

Chapter 4 Command Set 4-1014018MChapter 4@AABCName Read Alarm LimitDescription Request the alarm limits for the specified channel in the an

Page 97

4-102 ADAM 4000 Series User's ManualCommand Set4018M

Page 98

Chapter 4 Command Set 4-103Chapter 4CommandSyntaxCommandNameDescription I/O Module@AADI Read Digital I/Oand AlarmStatusThe addressed module re

Page 99 - ADAM-4017 Command Table

4-104 ADAM 4000 Series User's ManualCommand Set@AADIName Read Digital I/O and Alarm StateDescription The addressed analog input module is instruc

Page 100 - ADAM-4017+ Command Set

Chapter 4 Command Set 4-105Chapter 4Status Code DO0 DO1 DO2 DO3OO OFF OFF OFF OFFO1 OFF OFF OFF ONO2 OFF OFF ON OFFO3 OFF OFF ON ONO4 OFF ON O

Page 101 - Chapter 4

Chapter 2 Installation Guideline 2-9Chapter 22.3 Baud rate and ChecksumAdam modules contain EEPROMs to store configuration information andcali

Page 102

4-106 ADAM 4000 Series User's ManualCommand Set@AADOName Set Digital OutputDescription Sets the values of the module’s digital outputs (ON or OFF

Page 103 - ADAM-4018 Command Table

Chapter 4 Command Set 4-107Chapter 4@AADOExample command: @05DO01(cr)response: !05(cr)The analog input module at address 05h is instructed to

Page 104 - ADAM-4018+ Command Set

4-108 ADAM 4000 Series User's ManualCommand SetNOTICE: An analog input module requires a maximum of 2 secondsafter it received an Enable Alarm co

Page 105

Chapter 4 Command Set 4-109Chapter 4@AAEATExample command: @03EAL(cr)response: !03(cr)The analog input module at address 03h is instructed to

Page 106

4-110 ADAM 4000 Series User's ManualCommand Set@AAHIName Set High Alarm LimitDescription Downloads High alarm limit value into the addressed modu

Page 107 - (continued on following page)

Chapter 4 Command Set 4-111Chapter 4NOTICE: An analog input module requires a maximum of 2 secondsafter it received an Set Low Alarm command t

Page 108 - ADAM-4019 Command Table

4-112 ADAM 4000 Series User's ManualCommand Set@AADAName Disable AlarmDescription Disables all alarm functions of the addressed analog inputmodul

Page 109 - ADAM-4021 Command Table

Chapter 4 Command Set 4-113Chapter 4@AACAName Clear Latch AlarmDescription Both alarm states (High and Low) of the addressed analog inputmodul

Page 110 - ADAM-4050 Command Table

4-114 ADAM 4000 Series User's ManualCommand SetName Read High Alarm LimitDescription The addressed module is asked to return its High alarm limit

Page 111

Chapter 4 Command Set 4-115Chapter 4Name Read Low Alarm LimitDescription The addressed module is asked to return its Low alarm limitvalue.Synt

Page 113 - ADAM-4053 Command Table

2-10 ADAM 4000 Series User's ManualInstallation GuidelineChanging Baud rate and ChecksumBaud rate and checksum settings have several thing

Page 114 - ADAM-4055 Command Set Table

4-116 ADAM 4000 Series User's ManualCommand Set@AAREName Read Event CounterDescription The addressed module is instructed to return its event cou

Page 115 - ADAM-4060/4068 Command Table

Chapter 4 Command Set 4-117Chapter 4@AACEName Clear Event CounterDescription The addressed module is instructed to reset its event counter toz

Page 116 - ADAM-4080 Command Table

4-118 ADAM 4000 Series User's ManualCommand Set

Page 117

Chapter 4 Command Set 4-119Chapter 44016CommandSyntaxCommand Name DescriptionI/Omodule$AA6 Get ExcitationVoltage OutputValueReturns either las

Page 118

4-120 ADAM 4000 Series User's ManualCommand Set4016$AA6Name Get Excitation Voltage Output ValueDescription The addressed strain gauge input modul

Page 119

Chapter 4 Command Set 4-121Chapter 44016$AA7Name Excitation Voltage OutputDescription Send a value to the analog output channel of the address

Page 120 - ADAM-4080D Command Table

4-122 ADAM 4000 Series User's ManualCommand Set4016$AASName Start-up Voltage Output ConfigurationDescription Stores the present analog output val

Page 121

Chapter 4 Command Set 4-123Chapter 44016$AASExample command: $0AS(cr)response: !0A(cr)Presume the present output value of the output channel o

Page 122

4-124 ADAM 4000 Series User's ManualCommand Set4016$AAEName Trim CalibrationDescription Trims the output voltage of the strain gauge input module

Page 123

Chapter 4 Command Set 4-125Chapter 44016$AAAName Zero CalibrationDescription Stores the voltage output value of the addressed strain gaugeinpu

Page 124

Chapter 2 Installation Guideline 2-11Chapter 2Figure 2-4 Multi-module Connection2.4 Multiple Module HookupThe Figure below shows how ADAM mod

Page 125

4-126 ADAM 4000 Series User's ManualCommand Set4016$AABName Span CalibrationDescription Stores the voltage output value of the addressed strain g

Page 126

Chapter 4 Command Set 4-1274021Chapter 4Command Syntax Command Name DescriptionI/OModule%AANNTTCCFF Configuration Sets the address, output ran

Page 127

4-128 ADAM 4000 Series User's ManualCommand Set4021%AANNTTCCFFName ConfigurationDescription Sets address, input range, baud rate, data format, ch

Page 128 - 76543210

Chapter 4 Command Set 4-1294021Chapter 4Output RangeCode (Hex)Output Range forADAM 402130 0to20mA31 4to20mA32 0to10VBaud RateCode (Hex)Baud Ra

Page 129

4-130 ADAM 4000 Series User's ManualCommand Set4021%AANNTTCCFFExample command: %310A310610(cr)response: !24(cr)The analog input module at address

Page 130

Chapter 4 Command Set 4-1314021Chapter 4#AAName Analog Data OutDescription Send a value to the addressed analog output module. Uponreceipt, t

Page 131

4-132 ADAM 4000 Series User's ManualCommand Set4021#AAExample command: #3315.000(cr)response: >(cr)The command sends the value 15 mA to the an

Page 132

Chapter 4 Command Set 4-1334021Chapter 4$AA4Name Start-up Voltage/Current Output ConfigurationDescription Stores the present output value of a

Page 133

4-134 ADAM 4000 Series User's ManualCommand Set4021$AA3Name Trim CalibrationDescription Trims the addressed analog output module a specified numb

Page 134

Chapter 4 Command Set 4-1354021Chapter 4$AA3Example command: $07314(cr)response: !07(cr)The command tells the analog output module at address

Page 135

2-12 ADAM 4000 Series User's ManualInstallation Guideline2.5 Application ExampleADAM-4011 alarm functions may be used to build a simple ON

Page 136

4-136 ADAM 4000 Series User's ManualCommand Set4021$AA0Name 4 mA Calibration commandDescription Stores the current output value of the addressed

Page 137

Chapter 4 Command Set 4-1374021Chapter 4$AA1Name 20 mA Calibration commandDescription Stores the current output value of the addressed analog

Page 138 - 4018+, 4018M, 4019

4-138 ADAM 4000 Series User's ManualCommand Set4021$AA2Name Read Configuration Status commandDescription Instruct the addressed analog output mod

Page 139

Chapter 4 Command Set 4-1394021Chapter 4$AA6Name Last Value ReadbackDescription The addressed analog output module is instructed to return the

Page 140

4-140 ADAM 4000 Series User's ManualCommand Set4021$AA8Name Current ReadbackDescription The addressed analog output module is instructed to meas

Page 141

Chapter 4 Command Set 4-1414021Chapter 4$AA5Name Reset Status commandDescription Checks the Reset Status of the addressed analog output module

Page 142

4-142 ADAM 4000 Series User's ManualCommand Set4021$AAFName Read Firmware VersionDescription The command requests the analog output module at add

Page 143 - 4016, 4019

Chapter 4 Command Set 4-1434021Chapter 4$AAMName Read Module NameDescription The command requests the analog output module at addressAA to ret

Page 144

4-144 ADAM 4000 Series User's ManualCommand Set4021Spec :1. 4 CH 12-Bits Analog Output With 4 Isolation General Purpose / Emer-gency Control Digi

Page 145

Chapter 4 Command Set 4-1454021Chapter 4About System / CH SettingCommand Set Function Response Example Note T0#AACn(data) Direct Output CHn Da

Page 146 - 4011D, 4015

Chapter 2 Installation Guideline 2-13Chapter 2Figure 2-5 Simple ON/OFF Controller Function

Page 147

4-146 ADAM 4000 Series User's ManualCommand Set4021About System / CH SettingCommand Set Function Response Example Note T0$AA8Cn Read Back CHn Out

Page 148 - (number of counts)

Chapter 4 Command Set 4-1474021Chapter 4$025 !0200Now Reset Module 12 Times Never Use $025 Command$025 !020C$025 !0200If Input DAC Data Is Ove

Page 149 - 4015, 4019

4-148 ADAM 4000 Series User's ManualCommand Set4021(3) If Equal 4 mA Then Save Parameter( $020C2 ) And Goto Next Step Otherwise (1) Or (2)5. Rese

Page 150

Chapter 4 Command Set 4-1494021Chapter 4

Page 151

4-150 ADAM 4000 Series User's ManualCommand Set4021

Page 152 - JIS RTD 100O, α = 0.00391

Chapter 4 Command Set 4-1514050, 4052, 4053, 4060, 4051, 4055, 4068Chapter 4Command SyntaxCommandNameDescription I/O Module%AANNTTCCFF Configu

Page 153

4-152 ADAM 4000 Series User's ManualCommand Set4050, 4052, 4053, 4060, 4051, 4055, 406876543210%AANNTTCCFFName ConfigurationDescription Configure

Page 154

Chapter 4 Command Set 4-1534050, 4052, 4053, 4060, 4051, 4055, 4068Chapter 4Baud RateCode (Hex)Baud Rate03 1200 bps04 2400 bps05 4800 bps06 96

Page 155

4-154 ADAM 4000 Series User's ManualCommand Set4050, 4052, 4053, 4060, 4051, 4055, 4068$AA6Name Digital Data InDescription This command requests

Page 156

Chapter 4 Command Set 4-1554050, 4052, 4053, 4060, 4051, 4055, 4068Chapter 4$AA6Example command: $336(cr)response: !112200(cr)The first two ch

Page 157

2-14 ADAM 4000 Series User's ManualInstallation GuidelineProgramming ExampleThe following program is a simple program written in BASIC tha

Page 158

4-156 ADAM 4000 Series User's ManualCommand Set4050, 4052, 4053, 4060, 4051, 4055, 4068Since the ADAM-4060 has only four output channels all them

Page 159

Chapter 4 Command Set 4-1574050, 4052, 4053, 4060, 4051, 4055, 4068Chapter 44050, 4060, 4055, 4068#AABBResponse >(cr) if the command was va

Page 160

4-158 ADAM 4000 Series User's ManualCommand Set4050, 4052, 4053, 4060, 4051, 4055, 4068#**Name Synchronized SamplingDescription Orders all (analo

Page 161

Chapter 4 Command Set 4-1594050, 4052, 4053, 4060, 4051, 4055, 4068Chapter 4$AA4Name Read Synchronized DataDescription The addressed digital I

Page 162

4-160 ADAM 4000 Series User's ManualCommand Set4050, 4052, 4053, 4060, 4051, 4055, 4068$AA4(dataOutput) two-character hexadecimal value which eit

Page 163

Chapter 4 Command Set 4-1614050, 4052, 4053, 4060, 4051, 4055, 4068Chapter 4$AA2Name Configuration Status commandDescription Returns the confi

Page 164

4-162 ADAM 4000 Series User's ManualCommand Set4050, 4052, 4053, 4060, 4051, 4055, 4068Baud RateCode (Hex)Baud Rate03 1200 bps04 2400 bps05 4800

Page 165

Chapter 4 Command Set 4-1634050, 4052, 4053, 4060, 4051, 4055, 4068Chapter 4$AA5Name Reset Status commandDescription Requests the Reset Status

Page 166

4-164 ADAM 4000 Series User's ManualCommand Set4050, 4052, 4053, 4060, 4051, 4055, 4068$AA5Example command: $395(cr)response: !390(cr)The command

Page 167

Chapter 4 Command Set 4-1654050, 4052, 4053, 4060, 4051, 4055, 4068Chapter 4$AAFName Read Firmware VersionDescription The command requests the

Page 168

Chapter 2 Installation Guideline 2-15Chapter 2

Page 169

4-166 ADAM 4000 Series User's ManualCommand Set4050, 4052, 4053, 4060, 4051, 4055, 4068$AAMName Read Module NameDescription The command requests

Page 170

Chapter 4 Command Set 4-167Chapter 44080, 4080D4.7 Counter/Frequency Module Command4.7.1 Configuration, Counter Input and Display Command SetC

Page 171

4-168 ADAM 4000 Series User's ManualCommand Set4080, 4080DFigure 4-5 Data format for 8-bit parameterNot usedFrequency Gate Time0: 0.1 seconds1:

Page 172

Chapter 4 Command Set 4-169Chapter 44080, 4080DBaud RateCode (Hex)Baud Rate03 1200 bps04 2400 bps05 4800 bps06 9600 bps07 19.2 Kbps08 38.4 Kbp

Page 173

4-170 ADAM 4000 Series User's ManualCommand Set4080, 4080D$AA2Name Configuration StatusDescription The command requests the return of the configu

Page 174 - Channel 0

Chapter 4 Command Set 4-171Chapter 44080, 4080D$AAFName Read VersionDescription The command requests the analog input module at address AAto r

Page 175

4-172 ADAM 4000 Series User's ManualCommand Set4080, 4080D$AAMName Read Module NameDescription The command requests the counter/frequency module

Page 176

Chapter 4 Command Set 4-173Chapter 44080, 4080D$AABSName Set Input ModeDescription Set the input signal mode of the specified counter/frequenc

Page 177

4-174 ADAM 4000 Series User's ManualCommand Set4080, 4080D$AABName Read Input Mode.Description Read the input mode of the specified counter/frequ

Page 178

Chapter 4 Command Set 4-175Chapter 44080, 4080D#AANName: Read Counter or Frequency ValueDescription: Instructs the addressed counter/frequency

Page 179

2-16 ADAM 4000 Series User's ManualInstallation Guideline

Page 180

4-176 ADAM 4000 Series User's ManualCommand Set4080, 4080D$AA8VName Select LED Data OriginDescription Select whether LED will display data from t

Page 181 - Decimal point

Chapter 4 Command Set 4-177Chapter 44080, 4080D$AA8Name Read LED Data OriginDescription Read the LED Data Origin status which determines wheth

Page 182

4-178 ADAM 4000 Series User's ManualCommand Set4080, 4080D$AA9(data)Name Send Data to LEDDescription The host computer sends data to the addresse

Page 183

Chapter 4 Command Set 4-1794080, 4080DChapter 4CommandSyntaxCommand Name DescriptionI/OModule$AAAG Set Gate Mode Requests the specified counte

Page 184

4-180 ADAM 4000 Series User's Manual4080, 4080DCommand Set$AAAGName Set Gate Mode.Description Request the specified counter/frequency module to s

Page 185

Chapter 4 Command Set 4-1814080, 4080DChapter 4$AAAName Read Gate Mode.Description Request the specified counter/frequency module to return it

Page 186

4-182 ADAM 4000 Series User's Manual4080, 4080DCommand Set$AA3N(data)Name Set Maximum Counter ValueDescription Set the maximum value of counter 0

Page 187

Chapter 4 Command Set 4-1834080, 4080DChapter 4$AA3NName Read Maximum Counter ValueDescription Read the maximum counter value of the counter 0

Page 188

4-184 ADAM 4000 Series User's Manual4080, 4080DCommand Set$AA5NSName Start/Stop CounterDescription Request the addressed counter/frequency module

Page 189

Chapter 4 Command Set 4-1854080, 4080DChapter 4$AA5NName Read Counter Start/Stop StatusDescription Requests the addressed counter/frequency mo

Page 190

I/O Modules3

Page 191

4-186 ADAM 4000 Series User's Manual4080, 4080DCommand Set$AA6NName Clear CounterDescription Clears the counter 0 or counter 1 of the specified c

Page 192

Chapter 4 Command Set 4-1874080, 4080DChapter 4$AA7NName Read/Clear Overflow Flag.Description The command requests the addressed module to ret

Page 193

4-188 ADAM 4000 Series User's Manual4080, 4080DCommand Set

Page 194

Chapter 4 Command Set 4-1894080, 4080DChapter 4CommandSyntaxCommand Name Description I/O Module$AA4S Enable/DisableDigital FilterEnables or di

Page 195

4-190 ADAM 4000 Series User's ManualCommand Set4080, 4080D$AA4SName Enable/Disable Digital FilterDescription Enables or disables the digital filt

Page 196

Chapter 4 Command Set 4-1914080, 4080DChapter 4$AA4Name Read Filter StatusDescription Read the digital filter status of the addressed counter/

Page 197

4-192 ADAM 4000 Series User's ManualCommand Set4080, 4080D$AA0H(data)Name Set Minimum Input Signal Width at High LevelDescription: Set the minimu

Page 198

Chapter 4 Command Set 4-1934080, 4080DChapter 4$AA0HName: Read Minimum Input Signal Width at High Level.Description: Read the minimum input si

Page 199

4-194 ADAM 4000 Series User's ManualCommand Set4080, 4080D$AA0L(data)Name Set Minimum Input Signal Width at Low LevelDescription: Set the minimum

Page 200 - 4011, 4011D, 4012, 4014D

Chapter 4 Command Set 4-1954080, 4080DChapter 4$AA0LName: Read Minimum Input Signal Width at Low Level.Description: Read the minimum input sig

Page 201

I/O Modules3-2 ADAM 4000 Series User's Manual3.1 ADAM-4011/4011D/4012/4013/4015 Analog InputModulesAnalog input modules use a microprocessor-cont

Page 202

4-196 ADAM 4000 Series User's ManualCommand Set4080, 4080D$AA1H(data)Name: Set Non-isolated High Trigger Level.Description: Set the high trigger

Page 203

Chapter 4 Command Set 4-1974080, 4080DChapter 4$AA1HName: Read Non-isolated High Trigger Level.Description: Read the high trigger level for no

Page 204

4-198 ADAM 4000 Series User's ManualCommand Set4080, 4080D$AA1L(data)Name: Set Non-isolated Low Trigger Level.Description: Set the low trigger le

Page 205

Chapter 4 Command Set 4-1994080, 4080DChapter 4$AA1LName: Read Non-isolated Low Trigger Level.Description: Read the low trigger level for non-

Page 206

4-200 ADAM 4000 Series User's ManualCommand Set4080, 4080D

Page 207

Chapter 4 Command Set 4-201Chapter 44080CommandSyntaxCommand Name DescriptionI/OModule@AAPN(data) Set Initial CountValue of Counter NSets the

Page 208

4-202 ADAM 4000 Series User's Manual4080Command SetCommandSyntaxCommand Name DescriptionI/OModule@AAEAT Enable Alarm ofCounter 0Enable the alarm

Page 209

Chapter 4 Command Set 4-203Chapter 44080@AAPN(data)Name Set Initial Count Value of Counter 0 (or 1)Description Set the initial count value for

Page 210

4-204 ADAM 4000 Series User's Manual4080Command Set@AAGNName Read Initial Count Value of Counter 0 (or 1)Description Read the initial count value

Page 211

Chapter 4 Command Set 4-205Chapter 44080@AAEANName Enable AlarmDescription Enable Alarm for the specified counterSyntax @AAEAN (cr)@ is a deli

Page 212

Chapter 3Chapter 3 I/O Modules 3-3Event counting (Except ADAM-4013)The event counter is connected to the Digital Input channel and can beused t

Page 213

4-206 ADAM 4000 Series User's Manual4080Command Set@AADANName Disable AlarmDescription Disable Alarm for the specified counterSyntax @AADAN (cr)@

Page 214

Chapter 4 Command Set 4-207Chapter 44080@AAPA(data)@AASA(data)Name Set Alarm Limit Value of Counter 0 (or 1)Description Set the Alarm limit va

Page 215

4-208 ADAM 4000 Series User's Manual4080Command Set@AARP@AARAName Read Alarm Limit Value of Counter 0 (or 1)Description Read the alarm limit valu

Page 216

Chapter 4 Command Set 4-209Chapter 44080@AADOName Set Digital OutputDescription Set the values of the module’s two digital outputs (ON or OFF)

Page 217

4-210 ADAM 4000 Series User's Manual4080Command Set@AADIName Read Digital Output and Alarm StateDescription The addressed counter module is instr

Page 218

Chapter 4 Command Set 4-211Chapter 44080@AADIExample command: @15DI(cr) response: !1510000(cr)The counter module at address 15h is instructed

Page 219

4-212 ADAM 4000 Series User's Manual4080Command Set@AAEATName Enable AlarmDescription The addressed counter module is instructed to enable its al

Page 220

Chapter 4 Command Set 4-213Chapter 44080@AADAName Disable AlarmDescription Disable all alarm functions for counter 0 of the addressedcounter m

Page 221

4-214 ADAM 4000 Series User's Manual4080Command Set@AACAName Clear Latch AlarmDescription Both alarm states (High and Low) of the addressed count

Page 222

Chapter 4 Command Set 4-215Chapter 44080@AAPA(data)Name Set Low-alarm Count Value for Counter 0.Description Set the low-alarm count value for

Page 223

ADAM 4000 SeriesData Acquisition ModulesUser's ManualCopyright NoticeThis document is copyrighted, 1997, by Advantech Co., Ltd. All rights areres

Page 224

I/O Modules3-4 ADAM 4000 Series User's ManualFunction Description for the ADAM-4011 analog input moduleTo provide a better understanding of the f

Page 225

4-216 ADAM 4000 Series User's Manual4080Command Set@AASA(data)Name Set Hi-alarm Count Value of Counter 0.Description Set the high-alarm count val

Page 226

Chapter 4 Command Set 4-217Chapter 44080@AARPName Read Low-alarm Count Value of Counter 0Description Read the low-alarm value of counter 0 of

Page 227

4-218 ADAM 4000 Series User's Manual4080Command Set@AARAName Read High-alarm Count Value for Counter 0.Description Requests the addressed counter

Page 228

Calibration5

Page 229

Calibration5-2 ADAM 4000 Series User's ManualFigure 5-1 Applying Calibration VoltageAnalog input/output modules are calibrated when you receive

Page 230

Chapter 5Chapter 5 Calibration 5-3Figure 5-3 Span Calibration5. Execute the Span Calibration command. This can be done with theADAM utility sof

Page 231 - T1 : 100ms

Calibration5-4 ADAM 4000 Series User's Manual6. Only for ADAM 4011, 4011D, 4018, 4018+, 4018MExecute the CJC (cold junction sensor) calibration c

Page 232 - ADAM-4024 4CH AO Module

Chapter 5Chapter 5 Calibration 5-5NOTE:1 You can substitute 2.5 V for 20 mA if you remove the currentconversion resistor for that channel. Howe

Page 233

Calibration5-6 ADAM 4000 Series User's ManualModule Input Range Code (Hex) Input Range Span Calibration Voltage4016 –15 mV +15 mV–50 mV +50 mV–10

Page 234

Chapter 5Chapter 5 Calibration 5-7Use a precision resistance decade box or discrete resistors with values:10 W, 15 W, 60 W, 140 W, 200 W and 440

Page 235

Chapter 3Chapter 3 I/O Modules 3-5ADAM-4011Figure 3-1 ADAM-4011 Thermocouple Input Module Accepts:- J, K, T, E, R, S and B thermocouples- mill

Page 236 - %AANNTTCCFF

Calibration5-8 ADAM 4000 Series User's ManualModuleInput RangeCode (Hex)Input RangeSpan CalibrationResistanceOffset CalibrationResistance4013 201

Page 237

Chapter 5Chapter 5 Calibration 5-9Figure 5-6 Setup for Analog Output Calibration5.3 Analog Output CalibrationModel: ADAM-4021The output current

Page 238

Calibration5-10 ADAM 4000 Series User's Manual4. Issue the Analog Data Out command to the module with an outputvalue of 4 mA.5. Check the actual

Page 239

Chapter 5Chapter 5 Calibration 5-11Module: ADAM-40161. Apply power to the strain gauge input module and let it warm up forabout 30 minutes.2. As

Page 240 - 00001010

Calibration5-12 ADAM 4000 Series User's Manual4. Execute the Span Calibration command. This can be done with theADAM utility software. (See &quo

Page 241

ATechnical Specifications

Page 242

Technical specificationsA-2 ADAM 4000 Series User's ManualA.1 ADAM-4011 Thermocouple Input ModuleTable A-1 ADAM-4011 SpecificationsInput range J

Page 243

Appendix A Technical Specifications A-3Appendix ATable A-2 ADAM-4011 Range Accuracy for ThermocoupleInput RangeCode (Hex)Input Range TypicalA

Page 244

Technical specificationsA-4 ADAM 4000 Series User's ManualFigure A-1 ADAM-4011 Function Diagram

Page 245

Appendix A Technical Specifications A-5Appendix AA.2 ADAM-4011D Thermocouple Input Module with LEDDisplayTable A-3 ADAM-4011D Specifications

Page 246

I/O Modules3-6 ADAM 4000 Series User's ManualADAM-4011DFigure 3-2 ADAM-4011D Thermocouple Input Module with LED DisplayAccepts:- J, K, T, E, R,

Page 247

Technical specificationsA-6 ADAM 4000 Series User's ManualInput RangeCode (Hex)Input Range TypicalAccuracyMaximumErrorUnits0E J thermocouple 0 to

Page 248

Appendix A Technical Specifications A-7Appendix ARect &FilterPowerConverterPower Input+10 ~ +30 VDC+VP.S.+5 V GNDPowerIsolation-V16 BITA/D

Page 249

Technical specificationsA-8 ADAM 4000 Series User's ManualA.3 ADAM-4012 Analog Input ModuleTable A-5 ADAM-4012 SecificationsInput range ±150 mV,

Page 250

Appendix A Technical Specifications A-9Appendix AFigure A-3 ADAM-4012 Function Diagram

Page 251

Technical specificationsA-10 ADAM 4000 Series User's ManualTable A-6 ADAM-4013 SpecificationsInput range Pt and Ni RTDOutput RS-485 (2-Wire) sp

Page 252 - 7 6 5 4 3 2 1 0

Appendix A Technical Specifications A-11Appendix AFigure A-4 ADAM-4013 Function Diagram

Page 253

Technical specificationsA-12 ADAM 4000 Series User's ManualA.5 ADAM-4014D Analog Input Module with LED DisplayTable A-7 ADAM-4014D Specification

Page 254 - 4080, 4080D

Appendix A Technical Specifications A-13Appendix AFigure A-5 ADAM-4014D Function Diagram

Page 255

Technical specificationsA-14 ADAM 4000 Series User's ManualA.6 ADAM-4016 Strain Gauge Input ModuleTable A-8 ADAM-4016 SpecificationsInput range

Page 256

Appendix A Technical Specifications A-15Appendix AFigure A-6 ADAM-4016 Function DiagramRect &FilterPowerConverterPower Input+10 ~ +30 VD

Page 257

Chapter 3Chapter 3 I/O Modules 3-7Figure 3-3 ADAM-4012 Analog Input ModuleAccepts:- millivolt inputs ± 150 mV and ±500 mV- volt inputs: ±1 V,

Page 258

Technical specificationsA-16 ADAM 4000 Series User's ManualA.7 ADAM-4017, 4017+ 8-Channel Analog Input ModuleTable A-9 ADAM-4017 Specifications

Page 259

Appendix A Technical Specifications A-17Appendix AFigure A-7 ADAM-4017 Function Diagram

Page 260

Technical specificationsA-18 ADAM 4000 Series User's ManualTable A-10 ADAM-4018 SpecificationsAnalog input channels Eight differential for ADAM-

Page 261

Appendix A Technical Specifications A-19Appendix AInput RangeCode (Hex)Input Range TypicalAccuracyMaximumErrorUnits0E J thermocouple 0 to760 C

Page 262

Technical specificationsA-20 ADAM 4000 Series User's ManualADAM-4018A.9 ADAM-4018M 8-channel Analog Input Data LoggerRect &FilterPowerConvert

Page 263

Appendix A Technical Specifications A-21Appendix ATable A-12 ADAM-4018M SpecificationsAnalog input channels Six differentialTwo single-endedI

Page 264

Technical specificationsA-22 ADAM 4000 Series User's ManualInput RangeCode (Hex)Input Range TypicalAccuracyMaximumErrorUnits0E J thermocouple 0 t

Page 265

Appendix A Technical Specifications A-23Appendix AFigure A-9 ADAM-4018M Function DiagramRect &FilterPowerConverterPower Input+10 ~ +30 VD

Page 266

Technical specificationsA-24 ADAM 4000 Series User's ManualTable A-14 ADAM-4021 SpecificationsOutput range mA, VInput RS-485 (2-wire) speed (bp

Page 267

Appendix A Technical Specifications A-25Appendix AFigure A-10 ADAM-4021 Function Diiagram

Page 268

I/O Modules3-8 ADAM 4000 Series User's ManualFigure 3-4 ADAM-4013 RTD Input ModuleAccepts:- input from platinum and nickel RTDsDepending on the

Page 269

Technical specificationsA-26 ADAM 4000 Series User's ManualA.11 ADAM-4050 Digital I/O ModuleTable A-15 ADAM-4050 SpecificationsI/ O Channels 7 i

Page 270

Appendix A Technical Specifications A-27Appendix AFigure A-11 ADAM-4050 Function Diagram

Page 271

Technical specificationsA-28 ADAM 4000 Series User's ManualA.12 ADAM-4052 Isolated Digital Input ModuleTable A-16 ADAM-40521/4052 Specification

Page 272

Appendix A Technical Specifications A-29Appendix AFigure A-12 ADAM-4052 Function Diagram

Page 273

Technical specificationsA-30 ADAM 4000 Series User's ManualA.13 ADAM-4053 16-channel Digital Input ModuleTable A-17 ADAM-4053 SpecificationsI/ O

Page 274

Appendix A Technical Specifications A-31Appendix AFigure A-13 ADAM-4053 Function DiagramRect& FilterPowerConverterPower Input+10 ~ +30 VD

Page 275

Technical specificationsA-32 ADAM 4000 Series User's ManualA.14 ADAM-4060 Relay Output ModuleTable A-18 ADAM-4060 SpecificationsDigital ouput 4-

Page 276

Appendix A Technical Specifications A-33Appendix AFigure A-14 ADAM-4060 Function Diagram

Page 277

Technical specificationsA-34 ADAM 4000 Series User's ManualA.15 ADAM-4080 Counter/Frequency Input ModuleTable A-19 ADAM-4080 SpecificationsInput

Page 278 - $AA0L(data)

Appendix A Technical Specifications A-35Appendix AFigure A-15 ADAM-4080 Function DiagramRect& FilterPowerConverterPower Input+10 ~ +30 VD

Page 279

Chapter 3Chapter 3 I/O Modules 3-9Figure 3-5 Millivolt and Volt InputFigure 3-6 Thermocouple InputApplication WiringThe following gives you e

Page 280

Technical specificationsA-36 ADAM 4000 Series User's ManualA.16 ADAM-4080D Counter/Frequency Input Module with LED DisplayTable A-20 ADAM-4080

Page 281

Appendix A Technical Specifications A-37Appendix AFigure A-16 ADAM-4080D Function Diagram

Page 282

Technical specificationsA-38 ADAM 4000 Series User's Manual

Page 283

BData Formats andI/O Ranges

Page 284

B-2 ADAM 4000 Series User's ManualData Formats and I/O RangesInput Range Resolution–15mV,–50mV 1µV (three decimal places)– 100 mV, – 150 mV, – 50

Page 285

Appendix BAppendix B Data Formats and I/O Ranges B-3Example 1The input value is -2.65 and the corresponding analog input module isconfigured f

Page 286

B-4 ADAM 4000 Series User's ManualData Formats and I/O RangesExample 1The input value is +2.0 V. The input module is configured for a range of ±5

Page 287

Appendix BAppendix B Data Formats and I/O Ranges B-5When in the FSR mode, if a value exceeds the uppermost value of the inputrange, an overran

Page 288

B-6 ADAM 4000 Series User's ManualData Formats and I/O RangesThermocouple TypeTemperature Range(Degrees)Temperature Range(Hex)J 0 C to 760 C 0000

Page 289

Appendix BAppendix B Data Formats and I/O Ranges B-7B.1.4 OhmsTo indicate ohms, set bits 0 and 1 of the data format/checksum/integrationtime p

Page 290

I/O Modules3-10 ADAM 4000 Series User's ManualFigure 3-8 Digital Output used with SSR (HI-LO alarm)Figure 3-7 Process Current Input

Page 291

B-8 ADAM 4000 Series User's ManualData Formats and I/O RangesB.2 Analog Input RangesRangeCode(hex)InputRangeDescriptionData Formats +F.S. Zero -F

Page 292

Appendix BAppendix B Data Formats and I/O Ranges B-9RangeCode(hex)InputRangeDescriptionData Formats +F.S. Zero -F.S.DisplayedResolution08 – 10

Page 293

B-10 ADAM 4000 Series User's ManualData Formats and I/O RangesRangeCode(hex)Input RangeDescriptionData FormatsMaximumSpecitiedSignalMinimumSpecit

Page 294

Appendix BAppendix B Data Formats and I/O Ranges B-11RangeCode(hex)Input RangeDescriptionData FormatsMaximumSpecitiedSignalMinimumSpecitiedSig

Page 295 - (ADAM-4080)

B-12 ADAM 4000 Series User's ManualData Formats and I/O RangesNOTE:1 Resolution is one LSB of 16 bitsRangeCode(hex)Input RangeDescriptionData Fo

Page 296

Appendix BAppendix B Data Formats and I/O Ranges B-13B.3 Analog Output FormatsYou can configure ADAM analog output modules to receive data fro

Page 297

B-14 ADAM 4000 Series User's ManualData Formats and I/O RangesB.3.2 Percent of SpanThe Percent of Span format is employed by setting bits 0 and 1

Page 298

Appendix BAppendix B Data Formats and I/O Ranges B-15B.4 Analog Output RangesRangeCode(hex)Input RangeDescriptionData FormatsMaximumSpecitiedS

Page 299

B-16 ADAM 4000 Series User's ManualData Formats and I/O Ranges

Page 300

CTechnical Diagrams

Page 301

Chapter 3Chapter 3 I/O Modules 3-11Figure 3-9 RTD Inputs

Page 302

C-2 ADAM 4000 Series User's ManualTechnical DiagramsFigure C-1 ADAM Modules DimensionsC.1 ADAM Dimensions

Page 303 - Calibration

Appendix C Technical Diagrams C-3Appendix CFigure C-2 DIN-Rail AdapterC.2 InstallationC.2.1 DIN-Rail Mounting

Page 304 - Applying Calibration Voltage

C-4 ADAM 4000 Series User's ManualTechnical DiagramsFigure C-3 DIN-Rail Mounting

Page 305 - Zero Calibration

Appendix C Technical Diagrams C-5Appendix CFigure C-4 Panel Mounting Bracket DimensionsC.2.2 Panel Mounting

Page 306 - Cold Junction Calibration

C-6 ADAM 4000 Series User's ManualTechnical DiagramsFigure C-5 Panel Mounting

Page 307

Appendix C Technical Diagrams C-7Appendix CC.2.3 Piggyback StackFigure C-6 Piggyback Stack

Page 308

C-8 ADAM 4000 Series User's ManualTechnical Diagrams

Page 309 - Figure 5-5

Utility SoftwareDTogether with the ADAM modules you will find a utility disk containingutility software with the following capabilities:- Module confi

Page 310

Utility SoftwareD-2 ADAM 4000 Series User's ManualNormally you will use the Search command to scan the network. Highlightthe Search command on th

Page 311 - 5.3 Analog Output Calibration

Appendix D Utility Software D-3Appendix DHere there are three different options, Configure, Edit-data and Alarm/Counter. To change the basic s

Page 312

I/O Modules3-12 ADAM 4000 Series User's ManualADAM-4015 6-channel RTD Input ModuleA RTD module is popular for temperature measurement. Unlike the

Page 313

Utility SoftwareD-4 ADAM 4000 Series User's ManualThe Checksum and Baud rate options need special attention since they canonly be changed when an

Page 314

Appendix D Utility Software D-5Appendix DFileThis option allows you to update the status field and can gives you ahardcopy of all the connecte

Page 315 - Technical Specifications

Utility SoftwareD-6 ADAM 4000 Series User's ManualTerminal Emulation is a full screen version of Command Test. (See Figure D-4, below.) Previous

Page 316

Appendix D Utility Software D-7Appendix DD.2 ADAM-4018M Utility SoftwareThe ADAM-4018M is designed to add memory to the ADAM-4018. Tosimplify

Page 317 - Appendix A

Utility SoftwareD-8 ADAM 4000 Series User's ManualOperation settingThis screen allows users to "START/STOP" the storage function of the

Page 318 - ADAM-4011 Function Diagram

Appendix D Utility Software D-9Appendix DNOTE 1.When standalone mode (in Memory Configuration Settings) isset to "NO" and you want

Page 319

Utility SoftwareD-10 ADAM 4000 Series User's Manual

Page 320 - Technical specifications

ERS-485 NetworkEIA RS-485 is industry’s most widely used bidirectional, balancedtransmission line standard. It is specifically developed for industri

Page 321 - ADAM-4011D Function Diagram

E-2 ADAM 4000 Series User's ManualRS-485 NetworkADAM modules are fully isolated and use just a single set of twisted pairwires to send and receiv

Page 322

Appendix E RS-485 Network E-3Appendix EFigure E-1 DaisychainingStar LayoutIn this scheme the repeaters are connected to drop-down cables from

Page 323 - ADAM-4012 Function Diagram

Chapter 3Chapter 3 I/O Modules 3-13Application WiringFigure 3-11: ADAM-4015 RTD Input Module Wiring DiagramRTD 1+COM 0RTD 0-RTD 0+14RTD 1+COM 0

Page 324

E-4 ADAM 4000 Series User's ManualRS-485 NetworkFigure E-3 Random structureRandomThis is a combination of daisychain and hierarchical structure

Page 325 - ADAM-4013 Function Diagram

Appendix E RS-485 Network E-5Appendix EE. 2 Line TerminationEach discontinuity in impedance causes reflections and distortion.When an impedanc

Page 326

E-6 ADAM 4000 Series User's ManualRS-485 NetworkExample:Each input of the receivers has a nominal input impedance of 18 kWfeeding into a diode tr

Page 327 - ADAM-4014D Function Diagram

Appendix E RS-485 Network E-7Appendix ENOTICE: The recommended wiring method that causes a minimumamount of reflection is daisy chaining where

Page 328

E-8 ADAM 4000 Series User's ManualRS-485 NetworkIntelligent RS-485 ControlADAM-4510 and ADAM-4520 are both equipped with an I/O circuitwhich can

Page 329 - ADAM-4016 Function Diagram

A checksum helps you to detect errors in commands from the host to themodules, and in responses from the modules to the host. The feature addstwo extr

Page 330

How to use the Checksum featureF-2 ADAM 4000 Series User's ManualF.1 Checksum Enable/DisableTo enable configuration of a module’s checksum featur

Page 331 - ADAM-4017 Function Diagram

Appendix F How to use the Checksum feature F-3Appendix FExample 2This example explains how to calculate the checksum value of a ReadHigh alarm

Page 332 - ADAM-4018 Function Diagram

How to use the Checksum featureF-4 ADAM 4000 Series User's ManualHEX ASCII60 ’61 a62 b63 c64 d65 e66 f67 g68 h69 i6A j6B k6C l6D m6E n6F o70 p71

Page 333

Table of ContentsChapter 1 Introduction ... 1-11.1 Overview ...

Page 334

I/O Modules3-14 ADAM 4000 Series User's ManualTechnical specification of ADAM-4015Table 3-1: Technical specification of ADAM-4015Channel6Input Ty

Page 335

Chapter 3Chapter 3 I/O Modules 3-153.2 ADAM-4016 Analog Input/Output ModuleA strain gauge input module uses a microprocessor-controlled integra

Page 336

I/O Modules3-16 ADAM 4000 Series User's ManualAlarm signallingStrain Gauge input modules include High and Low alarm functions. Highand Low alarm

Page 337 - ADAM-4018M Function Diagram

Chapter 3Chapter 3 I/O Modules 3-17ADAM-4016Figure 3-12 ADAM-4016 Analog Input/Output ModuleAccepts:- millivolt inputs: ±15 mV, ±50 mV, ±100 m

Page 338

I/O Modules3-18 ADAM 4000 Series User's ManualFigure 3-13 Strain Gauge Voltage InputFigure 3-14 Strain Gauge Current InputApplication Wiring

Page 339 - ADAM-4021 Function Diiagram

Chapter 3Chapter 3 I/O Modules 3-19Figure 3-15 Digital Output used with SSR

Page 340

I/O Modules3-20 ADAM 4000 Series User's Manual3.3 ADAM-4017/4017+/4018/4018M/4018+ 8-channel AnalogInput ModulesADAM-4017/4018 8-channel Analog I

Page 341 - ADAM-4050 Function Diagram

Chapter 3Chapter 3 I/O Modules 3-21ADAM-4017+ 8-channel Differential Analog Input ModuleHere comes a solution to the demand for more channels o

Page 342

I/O Modules3-22 ADAM 4000 Series User's ManualADAM-4017CODE INPUT RANGE08090A0B0CDATAACQUISITIONMODULEVin 0+Vin 0-Vin 1+Vin 5+Vin 5-Vin 6+INIT*(Y

Page 343 - ADAM-4052 Function Diagram

Chapter 3Chapter 3 I/O Modules 3-23ADAM-4017+ 8-channel Differential Analog Input ModuleADAM-4017+CODE INPUT RANGE08090A0B0CDATAACQUISITIONMODU

Page 344

4.6 Digital I/O and Relay Output Module Command ... 4-1514.7 Counter/Frequency Module Command ...

Page 345 - ADAM-4053 Function Diagram

I/O Modules3-24 ADAM 4000 Series User's ManualJumper setting1. JP9 and JP10 (default setting is six differential and two single-ended)2. JP1~JP83

Page 346

Chapter 3Chapter 3 I/O Modules 3-25ADAM-4018Figure 3-18 ADAM-4018 8-channel Thermocouple Input ModuleChannels:- six differential, two single-e

Page 347 - ADAM-4060 Function Diagram

I/O Modules3-26 ADAM 4000 Series User's ManualADAM-4018MFigure 3-19 ADAM-4018M 8-channel Analog Input Data LoggerChannels:- six differential, tw

Page 348

Chapter 3Chapter 3 I/O Modules 3-27ADAM-4018+ 8-ch. Thermocouple Input ModuleADAM-4018+CODE INPUT RANGE0E0F101112DATAACQUISITIONMODULEVin0+Vin

Page 349 - ADAM-4080 Function Diagram

I/O Modules3-28 ADAM 4000 Series User's ManualChannel 8Input Type ThermocoupleT/C type and TemperatureRangeJ 0 ~ 760 CK 0 ~ 1000 CT -100 ~ 400 CE

Page 350 - LED Display

Chapter 3Chapter 3 I/O Modules 3-29Figure 3-21 Differential Input (CH0 to CH5)Figure 3-22 Single-ended Input (CH6 to CH7)Apllication WiringVi

Page 351 - ADAM-4080D Function Diagram

I/O Modules3-30 ADAM 4000 Series User's ManualApplication Wiringinternal Built 1200hm ResisterADAM-4017+ 8-ch. differential analog input module w

Page 352

Chapter 3Chapter 3 I/O Modules 3-3111Vin 0+Vin 0-Vin 1+Vin 1-T/C or 4~20mA+-ADAM-4018+ 8-ch. thermalcouple input module wiring diagram

Page 353 - I/O Ranges

I/O Modules3-32 ADAM 4000 Series User's Manual3.4 ADAM-4019 8-channel Universal Analog Input ModuleHere comes good news for users needing various

Page 354

Chapter 3Chapter 3 I/O Modules 3-33Application WiringFigure 3-26: ADAM-4019 Universal AI wiring diagramVin 1-Vin 1+Vin 0-Vin 0+14141250.1%Ω–0~2

Page 355

B.2 Analog Input Ranges ... B-8B.3 Analog Output Formats ...

Page 356

I/O Modules3-34 ADAM 4000 Series User's ManualTable 3-2: Technical specification of ADAM-4019Channel8Input Type V, m V, m A , T /CInput type andt

Page 357

Chapter 3Chapter 3 I/O Modules 3-353.5 ADAM-4021 Analog Output ModuleAnalog output module receives their digital input through an RS-485interfa

Page 358

I/O Modules3-36 ADAM 4000 Series User's ManualFigure 3-27 ADAM -4021 Analog Output ModuleDepending on its configuration settings the module acce

Page 359

Chapter 3Chapter 3 I/O Modules 3-37Application WiringFigure 3-28 Analog Output

Page 360 - Data Formats and I/O Ranges

I/O Modules3-38 ADAM 4000 Series User's Manual3.6 ADAM-4050/4051/4052/4053/4055 Digital I/O ModulesADAM-4050 Digital I/O ModuleThe ADAM-4050 fea

Page 361 - Appendix B

Chapter 3Chapter 3 I/O Modules 3-39ADAM-4050Figure 3-31 ADAM-4050 Digital I/O ModuleChannels:- 7 input channels- 8 output channelsDigital Inpu

Page 362

I/O Modules3-40 ADAM 4000 Series User's ManualADAM-4051Figure 3-32 ADAM-4051 16-channel Digital Input ModuleTechnical Specification of ADAM-4051•

Page 363

Chapter 3Chapter 3 I/O Modules 3-41Figure 3-33 ADAM-4052 Isolated Digital Input ModuleChannels: 8- 6 differential- 2 single endedDigital Input

Page 364

I/O Modules3-42 ADAM 4000 Series User's ManualADAM-4053Figure 3-34 ADAM-4053 16-channel Digital Input ModuleChannels: 16Digital Input:-Dry conta

Page 365 - B.3 Analog Output Formats

Chapter 3Chapter 3 I/O Modules 3-43ADAM-4055Figure 3-34 ADAM-4055 16-channel Digital I/O Module• Number of Input Channel : 8 (4-channel/group)•

Page 366

1Introduction

Page 367

I/O Modules3-44 ADAM 4000 Series User's Manual• Number of Output Channel: 8 (8-channel/group)• Optical Isolation: 2500 VDC• Opto-isolator respons

Page 368

Chapter 3Chapter 3 I/O Modules 3-45Figure 3-36 Contact Closure Input (ADAM-4050)Application WiringThe following give you examples of how to co

Page 369 - Technical Diagrams

I/O Modules3-46 ADAM 4000 Series User's ManualFigure 3-37 Digital Output used with SSR (ADAM-4050)Figure 3-38 Dry Contact Wiring (ADAM-4051)

Page 370 - C.1 ADAM Dimensions

Chapter 3Chapter 3 I/O Modules 3-47Figure 3-39 Wet Contact Wiring (ADAM-4051)Figure 3-40 Isolation Digital Input (ADAM-4052)

Page 371 - C.2 Installation

I/O Modules3-48 ADAM 4000 Series User's ManualFigure 3-42 Contact Closure Input (ADAM-4053)Figure 3-41 Wet Contact Input (ADAM-4053)

Page 372 - DIN-Rail Mounting

Chapter 3Chapter 3 I/O Modules 3-49-+LOADFigure 3-45 Digital Input Wet Contact Wiring (ADAM-4055)-++-ORFigure 3-43 Digital Output wiring (ADAM-

Page 373 - Figure C-4

I/O Modules3-50 ADAM 4000 Series User's ManualFigure 3-46 ADAM-4060 Relay Output ModuleContact rating for Form A and Form C:AC: 0.5 A / 120 VACD

Page 374 - Panel Mounting

Chapter 3Chapter 3 I/O Modules 3-51Figure 3-47 ADAM-4068 8-channel Relay Output ModuleContact Rating :AC 125 V @ 0.6 A; 250 V @ 0.3 ADC 30 V @

Page 375 - Piggyback Stack

I/O Modules3-52 ADAM 4000 Series User's ManualFigure 3-49 Form C relay output (ADAM-4060)Application WiringThe following gives you examples on h

Page 376

Chapter 3Chapter 3 I/O Modules 3-53RL4 NORL4 COMRL3 NORL3 COMFigure 3-50 Form C relay output (ADAM-4068)Figure 3-51 Form A relay output (ADAM

Page 377 - Utility Software

1-2 ADAM 4000 Series User's ManualIntroduction1.1 OverviewThe ADAM Series is a set of intelligent sensor-to-computer interfacemodules containing

Page 378 - Main screen

I/O Modules3-54 ADAM 4000 Series User's Manual3.8 ADAM-4080/4080D Counter/Frequency Input ModulesADAM-4080/4080D Counter/frequency input module h

Page 379 - Setup options

Chapter 3Chapter 3 I/O Modules 3-55External Control (Gate mode)Besides the GND and counter terminal each channel has a gate terminal toconnect

Page 380

I/O Modules3-56 ADAM 4000 Series User's ManualADAM-4080Figure 3-52 ADAM-4080 Counter/Frequncy Input ModuleChannels: Two independent 32-bit count

Page 381 - Zero Calibration

Chapter 3Chapter 3 I/O Modules 3-57ADAM-4080DFigure 3-53 ADAM-4080D Counter/Frequency Input Module with LED DisplayChannels: Two independent 32

Page 382 - Terminal Emulation

I/O Modules3-58 ADAM 4000 Series User's ManualFigure 3-54 Non-isolated InputFigure 3-55 Photo-isolated InputApplication WiringCounter InputGATE

Page 383

4Command Set

Page 384 - Alarm setting

Command Set4-2 ADAM 4000 Series User's Manual4.1 IntroductionTo avoid communication conflicts when several devices try to send data atthe same ti

Page 385

Chapter 4 Command Set 4-3Chapter 4Before the command set, we provide the I/O module commands searchtable to help you find the commands you wish

Page 386

Command Set4-4 ADAM 4000 Series User's ManualCommand Syntax Command Name Command Description Page No.%AANNTTCCFF Configuration Sets the address,

Page 387 - RS-485 Network

Chapter 4 Command Set 4-5Chapter 4Command Syntax Command Name Command Description Page No.@AADI Read Digital I/O andAlarm StatusThe addressed m

Page 388 - E.1 Basic Network Layout

Chapter 1 Introduction 1-3Chapter 1Connectivity and ProgrammingADAM modules can connect to and communicate with all computers andterminals. The

Page 389 - Star structure

Command Set4-6 ADAM 4000 Series User's ManualCommand Syntax Command Name Command Description Page No.%AANNTTCCFF Configuration Sets the address,

Page 390 - Random structure

Chapter 4 Command Set 4-7Chapter 4Command Syntax Command Name Command Description Page No.@AADI Read Digital I/O andAlarm StatusThe addressed m

Page 391 - E. 2 Line Termination

Command Set4-8 ADAM 4000 Series User's ManualCommand Syntax Command Name Command Description Page No.%AANNTTCCFF Configuration Sets the address,

Page 392

Chapter 4 Command Set 4-9Chapter 4Command Syntax Command Name Command Description Page No.@AADI Read Digital I/O andAlarm StatusThe addressed m

Page 393

Command Set4-10 ADAM 4000 Series User's ManualCommand Syntax Command Name Command Description Page No.%AANNTTCCFF Configuration Sets the address,

Page 394 - E.3 RS-485 Data Flow Control

Chapter 4 Command Set 4-11Chapter 4ADAM-4015 Command TableCommand Syntax Command Name Command Description Page No.%AANNTTCCFF Configuration Set

Page 395 - Checksum feature

Command Set4-12 ADAM 4000 Series User's ManualCommand Syntax Command Name Command Description Page No.%AANNTTCCFF Configuration Set the address,

Page 396 - F.1 Checksum Enable/Disable

Chapter 4 Command Set 4-13Chapter 4Command Syntax Command Name Command Description Page No.@AADI Read Digital I/O AndAlarm StatusAsk the addres

Page 397

Command Set4-14 ADAM 4000 Series User's ManualCommand Syntax Command Name Command Description Page No.$AA6 Get Excitation VoltageOutput ValueRetu

Page 398

Chapter 4 Command Set 4-15Chapter 4ADAM-4017 Command TableCommand Syntax Command Name Command Description Page No.%AANNTTCCFF Configuration Set

Commentaires sur ces manuels