Technical specifications of ADAM-5060
Points
6, two Form A and four Form C
Contact rating
AC: 125 V @ 0.6A; 250 V @ 0.3 A DC: 30
V @ 2 A; 110 V @ 0.6 A
Breakdown voltage
500 V
AC(50/60 Hz)
Relay on time (typical)
3 ms
Relay off time (typical)
1 ms
Total switching time
10 ms
Insulation resistance
1000 M min. @ 500 V
DC
Power consumption
0.7 W
Table 4-9: Technical specifications of ADAM-5060
4.6.2 ADAM-5068 relay output module
The ADAM-5068 relay output module provides 8 relay channels of Form A.
Switches can be used to control the solid-state relays.
Figure 4-23: ADAM-5068 module frontal view