Chapter 5
5-19
ADAM 4000 Series User’s Manual
4011, 4011D, 4012, 4013,
4016, 4017, 4018, 4018M
$AA1
Name Offset Calibration command
Description Calibrates an analog input module to correct for offset
errors.
Syntax $AA1(cr)
$ is a delimiter character.
AA (range 00-FF) represents the 2-character hexadecimal
address of the analog input module you want to calibrate.
1 is the Offset Calibration command.
(cr) is the terminating character, carriage return (0Dh).
Response !AA(cr) if the command is valid.
?AA(cr) if an invalid operation was entered.
There is no response if the module detects a syntax error or
communication error or if the specified address does not
exist.
!
delimiter character indicates a valid command was
received.
?
delimiter character indicates the command was invalid.
AA (range 00-FF) represents the 2-character hexadecimal
address of the analog input module.
(cr) represents terminating character, carriage return (0Dh).
In order to successfully calibrate an analog input module’s
input range, a proper calibration input signal should be
connected to the analog input module before and during the
calibration. (See also Chapter 8, Calibration)
NOTICE: An analog input module requires a maximum of 7 seconds to
perform auto calibration and ranging after it received an Offset
Calibration command. During this interval, the module can not
be addressed to perform any other actions.