ADAM-5000 6-67
Chapter 6
#aaSi #aaSi
Name All Analog Data In
Description Returns the input value of all channels for a specified
analog input module of a specified system in engineer-
ing units or two’s complement data format
Syntax #aaSi
# is a delimiter character.
aa (range 00-FF) represents the 2-character hexadecimal
address of the ADAM-5000 system you want to
interrogate.
Si identifies the I/O slot (i:0 to 3) of ADAM-5000 system
you want to read.
(cr) is the terminating character, carriage return (0Dh).
Response !(data)(data)(data)(data) (data)(data)(data)(data)(cr) if the
command is valid. (Engineering Unit Data Format)
!(dddd)(dddd)(dddd)(dddd)(dddd)(dddd)(dddd)(dddd)(cr) if
the command is valid. (Two’s Complement Data Format)
?aa(cr) if an invalid operation was entered.
There is no response if the module detects a syntax error
or communication error or if the specified address does
not exist.
! delimiter character indicating a valid command was
received.
? delimiter character indicating the command was
invalid.
(data) is the input value in engineering units of the
interrogated module of the specified system. The (data)
from all channels is shown in sequence from 7 to 0. If
(data)=” “, it means the channel is invalid.
(dddd) is the input value in two’s complement format of
Vue de la page 188