6-96 ADAM-5000
Command Set
#aaSiCj(data) #aaSiCj(data)
? delimiter character indicating the command was
invalid.
(cr) is the terminating character, carriage return (0Dh)
Example command: #33S1C115.000(cr)
response: >(cr)
The command instructs the module in slot 1 of the
ADAM-5000 system at address 33h to output a value of
15 mA from it's channel 1. The module should be an
analog output module with it's channel 1 configured for
a range of 0-20 mA or 4-20 mA. If it is an analog output
module configured for the range 0-10 V, it's output value
will be 10 V and the response will be ?33(cr).
5024 Analog Output