Advantech RS-485 Manuel d'utilisateur Page 196

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 348
  • Table des matières
  • DEPANNAGE
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 195
6-74 ADAM-5000
Command Set
$aaSiCjAh $aaSiCjAh
Name Read Alarm Mode
Description Returns the alarm mode for the specified channel in the
specified ADAM-5000 system.
Syntax $aaSiCjAh(cr)
$ is a delimiter character.
aa (range 00-FF) represents the 2-character hexadecimal
address of an ADAM-5000 system.
SiCj identifies the desired slot i (i : 0 to 3) and the
desired channel j (j : 0 to 7).
Ah is the Read Alarm Mode command.
h indicates alarm type and can have the value H = High
alarm, L = Low alarm
(cr) represents terminating character, carriage return
(0Dh)
Response !aas(cr) if the command was valid
There is no response if the system detects a syntax error
or communication error or if the specified address does
not exist.
! delimiter character indicating a valid command was
received.
aa represents the 2-character hexadecimal address of the
corresponding ADAM-5000 system.
s indicates alarm mode and can have the value M =
Momentary mode, L = Latching mode
(cr) represents terminating character, carriage return
(0Dh)
5013/5017/5017H/5018
Analog Input Alarm
Vue de la page 195
1 2 ... 191 192 193 194 195 196 197 198 199 200 201 ... 347 348

Commentaires sur ces manuels

Pas de commentaire