Command Set
$aaSiCj4 $aaSiCj4
Example command: $0AS1C14(cr)
response: !0A(cr)
Presume the present output value of channel 1 of slot 1
in the ADAM-5000 system at address 0Ah is 9.4 mA.
The command tells the analog output module to store
the present output value in its non-volatile memory.
When the system is powered up or reset, its default
output value will be 9.4 mA.
The response from the ADAM-5000 system at address
0Ah indicates the command has been received.
Note: An analog output module requires a maximum of 6
milliseconds after it receives a Startup Output
Current/Voltage Configuration command to let the
settings take effect. During this interval, the module
cannot be addressed to perform any other actions.